DL11-32 Residual Current
Circuit Breaker with Overcurrent Protection |
|
| Construction and Feature |
Provides protection against earth earth fault/leakage
current, short-circuit and overload
High short-circuit capacity
Provides complementary protection against direct contact by
human body
Effectively protects electric equipment against insulating failure
Contact position indication
Provides protection against over-voltage
Provides comprehensive protection to household and commercial
distribution systems Technical Data
Type: electronic type
Residual current characteristics: AC
Pole No. : 1P+N
Tripping curve: B, C
Rated short-circuit capacity: 10000A
Rated voltage: 230/240V AC
Rated frequency: 50/60Hz
Tripping duration: instantaneous<=0.1S
Electro-mechanical endurance: 4000 cycles
Connection terminal: pillar terminal with clamp
Connection capacity: Flexible conductor 10mm2
Installation: On symmetrical DIN rail 35mm Panel mounting
Wiring Diagram |
|
| Overall & installation dimensions |
 |
|
|